LEV testing frequency: the 14 month COSHH interval

Updated

The interval most people quote as annual is actually 14 months, and shorter for four listed processes. Here is the 14 month LEV rule as the regulation words it.

Get LEV testing quotes Answer a few questions and up to three workplace health and safety assessors send you their prices. Free, no obligation.

The general interval: at least once every 14 months

Regulation 9(2) of the Control of Substances Hazardous to Health Regulations 2002 requires the employer to ensure that engineering controls are thoroughly examined and tested. For local exhaust ventilation plant that means at least once every 14 months.

Where the plant is used with a process specified in Column 1 of Schedule 4, it is not more than the interval in Column 2 (legislation.gov.uk).

HSE's LEV guidance frames the same duty as keeping the system in efficient working order, plus a periodic thorough examination and test at least every 14 months (hse.gov.uk).

14 months, not 12. The extra two months exist so a site can keep testing in the same part of its year without ever drifting out of date. Most maintenance planners still book at 12 months to leave slack, which is sensible rather than required.

The Schedule 4 processes with shorter intervals

COSHH 2002 Schedule 4: processes with a shorter LEV examination interval
Process (Column 1)Maximum interval (Column 2)
Blasting carried out in or incidental to the cleaning of metal castings, in connection with their manufacture1 month
Jute cloth manufacture1 month
Processes, other than wet processes, in which metal articles other than of gold, platinum or iridium are ground, abraded or polished using mechanical power, in any room for more than 12 hours in any week6 months
Processes giving off dust or fume in which non-ferrous metal castings are produced6 months

Wording condensed from Schedule 4 to the Control of Substances Hazardous to Health Regulations 2002 (legislation.gov.uk). If your process is not in that Schedule, the 14 month interval applies.

The interval is a maximum, not a target

  • The overriding duty in regulation 9(1) is to keep the plant in an efficient state, in efficient working order, in good repair and in a clean condition. A system that fails between tests has to be dealt with then, not at the next examination.
  • A change of process, a new hood or a modified duct run changes what the system is meant to do, so it needs checking against the new intended performance rather than waiting out the 14 months.
  • Interim checks by your own maintenance staff (airflow indicators, filter condition, damper positions) are how most sites catch problems early. They do not replace the statutory examination and test.

Keeping the record

Regulation 9(4) requires the employer to keep a suitable record of every examination, test and repair, for at least 5 years from the date it was made. In practice that record, along with the commissioning data, is the file an HSE inspector asks for first.

Get LEV testing quotes

Answer a few questions and up to three workplace health and safety assessors send you their prices. Free, no obligation.

Your extraction

What kind of extraction do you have?

Count capture points, not machines: the biggest price driver.

  • Free, no obligation
  • Your details go to at most three testing companies
  • Takes about two minutes

Questions, answered directly

How often does LEV have to be tested in the UK?

At least once every 14 months for most systems, under regulation 9(2) of COSHH 2002. Four processes listed in Schedule 4 are shorter. Blasting incidental to the cleaning of metal castings, and jute cloth manufacture: 1 month. Certain mechanical grinding, abrading or polishing of metal articles, and processes producing non-ferrous metal castings: 6 months.

Is LEV testing annual or every 14 months?

The legal maximum is 14 months, not 12. Many sites book annually to leave slack in the schedule. But the duty in COSHH regulation 9(2) is that the interval must not exceed 14 months, or the shorter Schedule 4 interval where that applies.

How long do I have to keep LEV test records?

At least 5 years from the date the record was made, under COSHH 2002 regulation 9(4). The record covers examinations, tests and repairs, and should be kept with the system's commissioning data.

What is the 14 month LEV rule?

COSHH regulation 9(2) requires local exhaust ventilation to be thoroughly examined and tested at least once every 14 months. It must be more often where it serves a process listed in Schedule 4. The 14 months is a ceiling, so most employers book every 12 months and keep two months in hand. (COSHH regulation 9, legislation.gov.uk)

Sources

This site's own dataset, every figure quoted from its source and dated:

  • The median published figure in the LEV Testing Price Index is 175 GBP across 7 sources' own pages (range 125 to 295 GBP), read 11 November 2026.
  1. legislation.gov.uk, COSHH 2002 regulation 9: maintenance, examination and testing of control measures
  2. legislation.gov.uk, COSHH 2002 Schedule 4: frequency of thorough examination and test of LEV plant
  3. HSE, local exhaust ventilation frequently asked questions
  4. HSE, HSG258 Controlling airborne contaminants at work: a guide to LEV